Type 1 vs Type 2 Surge Protection Devices: What Is the Difference?

Type 1 devices handle partial lightning current at the service entrance; Type 2 devices limit induced and switching surges in distribution boards. Here is how to choose.

By AZGA ELECTRIC6 min read

Hakel surge protection devices graphic with lightning over buildings
On this page
  1. Test classes in IEC 61643-11
  2. When do you need Type 1?
  3. Where Type 2 fits
  4. Coordination matters

Test classes in IEC 61643-11

IEC 61643-11 classifies SPDs by the type of test impulse they are designed for. The class tells you where in the installation the device belongs.

Type 1 (Class I)Type 2 (Class II)Type 3 (Class III)
Test impulse10/350 µs (Iimp)8/20 µs (In, Imax)Combination wave (Uoc)
Typical locationService entrance / main boardSub-distribution boardsClose to sensitive equipment
Protects againstPartial direct lightning currentInduced lightning and switching surgesResidual surges

When do you need Type 1?

Type 1 (or combined Type 1+2) devices are required where part of a direct lightning current can enter the installation — typically buildings with an external lightning protection system, or supplies fed by overhead lines. They are installed at the origin of the installation, between lightning protection zones LPZ 0 and LPZ 1.

Spark-gap based arresters such as the Hakel HLA50-255 are built for this impulse current duty. Combined T1+T2 arresters such as the HLSA25-275 series cover both duties in one device.

Where Type 2 fits

Type 2 SPDs are the workhorse of distribution and control panels. They limit surges that are induced into the network or created by switching, and they are installed in sub-distribution boards and machine panels (LPZ 1 → LPZ 2). Combined Type 2+3 devices such as the Hakel HSA-275 M S family can be used close to the equipment they protect.

Coordination matters

Protection is most effective when devices are coordinated: a Type 1 device takes the bulk of the energy, while downstream Type 2 and Type 3 devices bring the residual voltage down to a level the equipment can tolerate. Follow the manufacturer’s guidance on cable length or decoupling between stages, and always size the back-up fuse according to the datasheet.

Frequently asked questions

Can I install only a Type 2 SPD in a building with a lightning rod?

Where an external lightning protection system is present, a Type 1 (or Type 1+2) device is normally required at the service entrance. Check local regulations and the SPD manufacturer’s guidance.

What does “1+1” or “3+1” mean?

It describes the configuration: “3+1” means three protection modules between the phases and neutral plus one between neutral and PE, typically for TT or TN-S systems.