Why control enclosure temperature?
Drives, power supplies and PLCs generate heat, and many electronic components are rated for a maximum ambient temperature inside the panel. In humid climates, condensation during cool nights is just as harmful. A small enclosure thermostat switches a filter fan or heater automatically to keep conditions within limits.
NO vs NC contacts
| Contact | Behaviour | Controls | Examples |
|---|---|---|---|
| NO (normally open) | Closes when temperature rises above set point | Fans, filter fans, coolers | Plastim PTVT, Alfa THV2 |
| NC (normally closed) | Opens when temperature rises above set point | Heaters | Plastim PTHT, Alfa THR2 |
| NO + NC | Two independent set points | Fan and heater | Alfa THRV22 |
What else to check
- Setting range – e.g. 0–60 °C on the models above.
- Contact rating – Plastim PTHT/PTVT list 10 (2) A at 250/120 V AC; use an interposing relay or contactor for larger loads.
- Mounting – clip-on for 35 mm DIN rail.
- Position – mount away from direct heat sources and airflow paths so the sensor reads representative air temperature.
คำถามที่พบบ่อย
Can one thermostat control both a fan and a heater?
Yes, a dual thermostat with one NO and one NC contact (such as THRV22) can control both with separate set points.