Skip to content
Hakel HSA-275 M S – Surge Arrester – Type 2+3 (Class II+III), 1 PoleClick to zoom

HSA-275 M S

Surge Arrester – Type 2+3 (Class II+III), 1 Pole

Brand:
Hakel
Model:
HSA-275 M S
Series / group:
G-Line

HSA-275 M S (Surge Arrester) : TYPE 2+3, CLASS II+III

Key specifications

Class
Type 2+3 (Class II+III)
Uc
275 V
Imax (8/20)
50 kA
Up
< 1.25 kV
Download Datasheet

Prefer to talk? Call 02 194 0672

Overview

Surge arresters type T2+T3 ensure the equipotential bonding and reduce switching, induced and residual overvoltage in LV power supply systems. The products consist of varistors with big discharge ability. In 1+1 and 3+1 configurations they are additionaly combined with a gas discharge tube, which ensures zero leakage current through the PE conductor. Installed at the boundaries of LPZ 1 – LPZ 3 into subsidiary switchboards and control panels. If the product contains two PE (or PEN) terminals, it must not be used as a PE (PEN) bridge. M indication specifies a type of construction with removable module. S indication specifies a version with remote monitoring.

Technical Specifications

Technical Data

Test class according to EN 61643-11:2012 (IEC 61643-11:2011)T2, T3
SystemTN
Number of poles1
Rated operating AC voltageUN230 V
Maximum continuous operating voltage ACUC275 V
Maximum discharge current (8/20)Imax50 kA
Nominal discharge current for class II test (8/20)In20 kA
Open circuit voltage of the combination wave generatorUOC6 kV
Voltage protection level at InUp< 1.25 kV
Voltage protection level at UOCUp< 0.85 kV
Temporary overvoltage test (TOV) for tT = 5 sUT337 V
Temporary overvoltage test (TOV) for tT = 120 minUT440 V
Response timetA< 25 ns
Maximal back-up fuse160 A gL/gG
Residual currentIPE≤ 450 µA
Short-circuit current rating at maximum back-up fuseISCCR60 kArms
Lightning protection zoneLPZ1, LPZ2, LPZ3
Housing materialPolyamid PA6, UL94 V-0
Degree of protectionIP20
Operating temperatureϑ- 40 ÷ 70 °C
Humidity rangeRH5 ÷ 95 %
Minimum cross-section of connected Cu conductors accord. to HD 60364-5-534:2016 (doesn't apply to „V“ connection) for T2S2.5 mm² (L, N) 6 mm² (PE, PEN)
Clamp fastening range (solid conductor)1.5 ÷ 25 mm2
Clamp fastening range (stranded conductor)1.5 ÷ 16 mm2
Tightening moment3
InstallationOn DIN rail 35 mm
Modular width1
Operating positionAny
Product placement environmentInternal
Signalling at the deviceOptic
Importance of local signalingOK – clear target FAULT – red target
Remote signallingYes
Potential free signal contact (S) (recommended cross-section of remote monitoring max. 1 mm2)AC: 250 V / 1.5 A, DC: 250 V / 0.1 A
Modular designYes
Article number of spare module27 086
Lifetime> 100 000 h

Dimensions & Technical Drawings

HSA-275 M S – Dimension drawing
Dimension drawing
HSA-275 M S – Internal wiring diagram
Internal wiring diagram
HSA-275 M S – Installation diagram
Installation diagram

Downloads & Resources

Need pricing or a technical recommendation?